Single-stage 96–97% condensing furnace with a 9-speed ECM and one pressure switch. SS-AR9S96_AD9S96-R32 / wiring 0140F20003-B: 7-seg E0–E7 only (no E8/E9). Heat default F02, cool/Y/G default F04, F01 not recommended for heating. Conventional 24V. This is not the Goodman GR9S96 EE0/EE1/EE2 card and not AR9T96 dual-PS.
Not AR9T96 (two-stage, dual PS, E8/E9 high-fire, heat low F01 / high F02, LPM-34 on most upflow). Not AR9S80 (80% Cat I 4" metal vent, LPM-31, E2 is a chimney). Not ARVT96 / AMVC96 (ComfortBridge communicating VS). Not AM9S96 (LED 1–9 flash). Not Goodman GR9S96 (three-character EE card — this Amana door is single-E + digit on 0140F20003-B).
Reset only after the cause is fixed. Recurring rollout is a CO / fire call.
En
Igniter open
lockout
Igniter circuit measures open.
Ohms at the igniter plug, then at the IFC.
Harness rub-through on the collector.
EEH
Grounding error
lockout
IFC failed its ground check (sister to EA).
Green ground to cabinet and IFC.
Painted screw, missing star washer.
LE1 / UE2
Circulator current
lockout
ECM current too low (LE1) or unexpected (UE2).
Harness seated at motor and IFC. 9-speed ECM is tap-driven — a half-seated plug throws these.
Locked rotor, wet winding, or wrong motor for the cabinet.
Do not put a PSC motor or a ComfortBridge serial ECM on this IFC.
FE3 / LE4 / SE5 / rE6
A2L mitigation
hazard
Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.
Only valid on A2L pairs. On 410A, this is a miswired mitigation harness.
Leak sensor location, ventilation blower, and OEM mitigation sequence before you condemn the IFC.
Workflows
No heat on W
Tstat calling heat, indoor is cold, or E0/E2/E7.
Read the 7-seg before you pull power. Write E0–E7 — not GR9S96 EE0 and not AR9T96 E8/E9.
Door switch in? 120 VAC at L1, 24 VAC across the fuse (E5 if open).
W present at the IFC (not just at the stat). R to W ~24 VAC. A leftover W2 from a two-stage swap does nothing here — cap it.
Inducer on? If silent → inducer / IFC output. If running and E2 → trap, hose, the only PS, PVC vent.
If E1 with inducer off → unplug the only PS. Code change = switch/hose. No change = IFC.
HSI glow? No glow + En/E7 → igniter. Glow but no flame → gas cock, valve 24 VAC, manifold.
Flame then drop → µA on E6, ground, or rollout (Ed). Do not keep cycling.
E3 limit trips
Blower on, burners drop, E3.
Heat tap first. Factory default is F02. F01 is marked not recommended for heating on SS-AR9S96 p.7 — move off F01 before you change a limit.
Total external static vs the AR9S96 blower chart for this cabinet (A/B/C/D).
Filter, wheel, coil. Bottom return: SS note — failure to unfold the flanges can cut airflow ~18%.
Clock the meter / manifold — overfire trips limits with a clean filter.
Secondary / condensate — a drowned coil raises head in the exchanger and trips limit.
Which Amana 96% is this?
Plate is oily or the last tech mixed boards.
Door card 0140F20003-B + single 7-seg E0–E7 + one PS + 9-speed taps = AR9S96. Stay here.
Door card 0140F20004-B + E8/E9 on the sticker + two PS hoses = AR9T96. Leave this page.
ComfortBridge triple 7-seg + menu buttons + 14-pin serial motor = ARVT96 (new) or AMVC96 (older). Wrong chart.
Red LED flash 1–9, no 7-seg = AM9S96. Wrong chart.
Three-character EE0 / EE1 / EE2 on a Goodman door = GR9S96. Same one-PS physics, different card — use that chart.
Test points
Pressure switch
One NO switch. Closed only after inducer is up. There is no high-fire hose.
Manifold
Single-stage plate value only — no low/high pair. Rating plate wins.
Flame rod
Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use an 80% Norton chart.
ECM taps
Heat default F02. Cool/Y/G default F04. F01 not recommended for heating (SS p.7). Rise is cabinet-specific (25–55 on 0403AN through 35–65 on 80–120 kBtu).
Gotchas
Looks like AR9T96 until you count pressure-switch hoses. One hose = this page. Two hoses = AR9T96.
Goodman GR9S96 is not this door card. GR9S96 speaks EE0/EE1/EE2. This Amana card is E0–E7 on 0140F20003-B.
LPM-33 is the LP kit on both upflow and downflow. Do not grab LPM-34 (AR9T96 / ARVT96) or LPM-31 (AR9S80).
F01 on heat is an E3 callback. SS marks it not recommended for heating. Leave heat on F02 unless the rise chart says otherwise.
Bottom return: unfold the flanges. SS notes ~18% airflow loss if you leave them folded.
1205D is 3" vent only. A 2" concentric (72950) is not listed for that cabinet — use 72951.
A leftover W2 from a previous two-stage furnace does nothing useful here and confuses the next tech. Cap it.
Related plates
amana-ar9t96 — Two-stage 9-speed cousin — dual PS, 0140F20004-B, E8/E9 high fire. Wrong chart if you only have one hose.
amana-ar9s80 — 80% single-stage 9-speed — Cat I 4" metal vent, 0140F20001-B, LPM-31. E2 is a chimney, not a trap.
amana-arvt96 — ComfortBridge two-stage VS R-32. Triple 7-seg + serial ECM. Not this tap IFC.
amana-am9s96 — Older single-stage 96% flash sibling. LED 1–9, not this 7-seg E-card.
goodman-gr9s96 — Goodman single-stage 9-speed cousin — EE0/EE1/EE2 three-character card, not this E0–E7 door.