Amana

AR9S96

Furnace · Single-stage · 9-speed ECM · 96–97% AFUE · R-32 capable

Single-stage 96–97% condensing furnace with a 9-speed ECM and one pressure switch. SS-AR9S96_AD9S96-R32 / wiring 0140F20003-B: 7-seg E0–E7 only (no E8/E9). Heat default F02, cool/Y/G default F04, F01 not recommended for heating. Conventional 24V. This is not the Goodman GR9S96 EE0/EE1/EE2 card and not AR9T96 dual-PS.

Not AR9T96 (two-stage, dual PS, E8/E9 high-fire, heat low F01 / high F02, LPM-34 on most upflow). Not AR9S80 (80% Cat I 4" metal vent, LPM-31, E2 is a chimney). Not ARVT96 / AMVC96 (ComfortBridge communicating VS). Not AM9S96 (LED 1–9 flash). Not Goodman GR9S96 (three-character EE card — this Amana door is single-E + digit on 0140F20003-B).

Walk this in Diagnose

This plate

Input / AFUE
40–120 kBtu · 96–97% AFUE (SS-AR9S96_AD9S96-R32 May 2025) · 40 ng/J Low NOx, not SCAQMD/SJV
SKUs (upflow)
AR9S960403AN / 0603BN / 0803BN / 0804CN / 0805CN / 1005CN / 1205DN
SKUs (downflow)
AD9S960403BN / 0603BN / 0804CN / 1005CN / 1205DN
Staging
Single-stage gas valve · single-speed inducer · one pressure switch (0140F20003-B)
Blower
9-speed ECM taps F01–F09. Heat default F02. Cool/Y/G default F04. F01 not recommended for heating.
Heat exch.
Stainless tubular primary + stainless secondary
Ignition
120 VAC silicon nitride HSI · 115 VAC 60 Hz
Vent
Cat IV PVC 2–3" (3" on 1205D) · 2-pipe or 1-pipe · 24" front service
Tstat
Conventional 24V · W Y G R C — leftover W2 is unused. No ComfortBridge data pair.
Accessories
LPM-33 LP on BOTH upflow and downflow · HASFK-4 NG (0403AN TBD) / HASFK-6 or -5 LP · 72950 2" concentric (not 1205D) / 72951 3" · RF000142 · EFR02 · 0170K00000S/00001S · AFE18-60A · 0270F20723 (upflow) / 0270F05405 (downflow) · CFSB17/21/24 downflow sub-bases
Sister SKU
AD9S96 downflow. Looks like AR9T96 cabinet. Not GR9S96 (different EE door card).

This board

Self-diagnostic IFC · single 7-segment · wiring 0140F20003-B

  • door card is wiring 0140F20003-B. Read left to right (Seg3→Seg2→Seg1). Do not kill power — that clears the active code.
  • This card prints E0–E7, EA, Eb, Ec, Ed, En — single E plus a character. That is not Goodman GR9S96 EE0 / EE1 / EE2 (three characters).
  • One pressure switch only. E1 = stuck closed. E2 = open with inducer on. There is no E8/E9 high-fire pair — leave the AR9T96 page.
  • A2L pair codes (FE3, LE4, SE5, rE6) only apply when this furnace is tied to an R-32 / A2L outdoor. Ignore them on R-410A pairs.

Sequence

  1. W. IFC proves limits/rollout closed, starts the single-speed inducer.
  2. Prove PS. The only pressure switch must close. Already closed with inducer off → E1. Never closes → E2.
  3. HSI / valve. Silicon nitride warm-up, then the single solenoid. Open igniter → En / E7. Failures stack toward E0.
  4. Blower. Heat-on delay, then the 9-speed ECM on the selected heat tap (factory F02). Wrong tap / F01 on heat is the silent E3.
  5. Satisfied. Valve off, inducer post-purge, blower heat-off delay. Unexpected flame after valve-off → E4.

Faults on this IFC

  • E0

    Retry / recycle lockout

    lockout

    Too many failed ignition attempts or flame losses on this call.

    • Watch one full try: inducer, HSI glow, valve click, flame, µA.
    • Gas supply and manifold vs this plate (single-stage — no low/high pair).
    • Ground and flame-rod cleanliness.
    • Do not keep resetting — find which step dies.
  • E1

    PS stuck closed

    lockout

    The only pressure switch is made with the inducer off.

    • Unplug the only PS. If the code changes, switch is welded or the hose is holding residual draft.
    • Hose routed downhill to the collector? Water in the hose fakes a closed switch.
    • IFC input shorted — only after the switch ohms open.
    • There is no second (high-fire) switch to confuse with E8.
  • E2

    PS open

    lockout

    Inducer is on and the only switch will not close. Classic overnight 96% collector / trap call.

    • Inducer spinning? 120 VAC at the inducer on a W call.
    • Collector box, inducer outlet, and condensate trap — this 96% will not make pressure with a full trap.
    • PVC intake/exhaust (bird screen, ice, long run, wind). 1205D is 3" vent — a 2" termination is undersized.
    • Hose dry and on the only collector tap. There is no high-fire hose to move.
  • E3

    Open high limit

    warn

    Primary limit opened. Airflow or overfire — not a charge problem.

    • This is a 9-speed ECM. Heat default is F02. F01 is marked not recommended for heating on SS p.7 — that tap is an E3 generator.
    • Filter, blower wheel, A-coil, TES vs the AR9S96 blower chart for this cabinet.
    • Manifold vs rating plate — overfire trips limits with a clean filter.
    • Limit ohms after it cools.
  • E4

    Flame when valve should be off

    hazard

    Rod sees flame with the solenoid de-energized.

    • Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
    • Rod shorted to ground or IFC flame circuit.
  • E5

    Open fuse

    warn

    3 A (typical) automotive fuse on the IFC is open.

    • 24 V short on W, Y, G, humidifier, or EAC.
    • Unplug tstat harness and replace fuse. If it blows again the short is on the board or gas valve harness.
  • E6

    Low flame signal

    warn

    Flame is present but µA is below the IFC threshold.

    • Clean rod with a non-scratch pad — not sandpaper.
    • Chassis ground to burner box and IFC.
    • Manifold pressure / orifice / LP conversion (this plate uses LPM-33, not LPM-34).
  • E7

    Igniter relay fault

    lockout

    IFC did not see the igniter circuit behave as commanded.

    • Igniter ohms cold (confirm sticker — nitride, not an 80% Norton chart).
    • 120 VAC to igniter during warm-up.
    • Cracked nitride element.
  • EA

    Line polarity / ground

    lockout

    L1/N reversed or chassis ground missing. HSI and flame sense both suffer.

    • Hot and neutral at the IFC, not just the disconnect.
    • Burner box to IFC ground screw.
  • Eb / Ec

    Gas valve circuit

    lockout

    Internal (Eb) or external (Ec) gas-valve electrical fault.

    • Valve coil ohms, 24 VAC at the harness during trial.
    • Do not apply 24 V to a leaking valve as a ‘test’ and walk away.
  • Ed

    Open rollout

    hazard

    Manual-reset rollout opened. Treat as flame outside the exchanger until proven otherwise.

    • Primary exchanger cracks, burner alignment, crossover.
    • Blocked secondary / condensate / flue.
    • Reset only after the cause is fixed. Recurring rollout is a CO / fire call.
  • En

    Igniter open

    lockout

    Igniter circuit measures open.

    • Ohms at the igniter plug, then at the IFC.
    • Harness rub-through on the collector.
  • EEH

    Grounding error

    lockout

    IFC failed its ground check (sister to EA).

    • Green ground to cabinet and IFC.
    • Painted screw, missing star washer.
  • LE1 / UE2

    Circulator current

    lockout

    ECM current too low (LE1) or unexpected (UE2).

    • Harness seated at motor and IFC. 9-speed ECM is tap-driven — a half-seated plug throws these.
    • Locked rotor, wet winding, or wrong motor for the cabinet.
    • Do not put a PSC motor or a ComfortBridge serial ECM on this IFC.
  • FE3 / LE4 / SE5 / rE6

    A2L mitigation

    hazard

    Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.

    • Only valid on A2L pairs. On 410A, this is a miswired mitigation harness.
    • Leak sensor location, ventilation blower, and OEM mitigation sequence before you condemn the IFC.

Workflows

No heat on W

Tstat calling heat, indoor is cold, or E0/E2/E7.

  1. Read the 7-seg before you pull power. Write E0–E7 — not GR9S96 EE0 and not AR9T96 E8/E9.
  2. Door switch in? 120 VAC at L1, 24 VAC across the fuse (E5 if open).
  3. W present at the IFC (not just at the stat). R to W ~24 VAC. A leftover W2 from a two-stage swap does nothing here — cap it.
  4. Inducer on? If silent → inducer / IFC output. If running and E2 → trap, hose, the only PS, PVC vent.
  5. If E1 with inducer off → unplug the only PS. Code change = switch/hose. No change = IFC.
  6. HSI glow? No glow + En/E7 → igniter. Glow but no flame → gas cock, valve 24 VAC, manifold.
  7. Flame then drop → µA on E6, ground, or rollout (Ed). Do not keep cycling.

E3 limit trips

Blower on, burners drop, E3.

  1. Heat tap first. Factory default is F02. F01 is marked not recommended for heating on SS-AR9S96 p.7 — move off F01 before you change a limit.
  2. Total external static vs the AR9S96 blower chart for this cabinet (A/B/C/D).
  3. Filter, wheel, coil. Bottom return: SS note — failure to unfold the flanges can cut airflow ~18%.
  4. Clock the meter / manifold — overfire trips limits with a clean filter.
  5. Secondary / condensate — a drowned coil raises head in the exchanger and trips limit.

Which Amana 96% is this?

Plate is oily or the last tech mixed boards.

  1. Door card 0140F20003-B + single 7-seg E0–E7 + one PS + 9-speed taps = AR9S96. Stay here.
  2. Door card 0140F20004-B + E8/E9 on the sticker + two PS hoses = AR9T96. Leave this page.
  3. ComfortBridge triple 7-seg + menu buttons + 14-pin serial motor = ARVT96 (new) or AMVC96 (older). Wrong chart.
  4. Red LED flash 1–9, no 7-seg = AM9S96. Wrong chart.
  5. Three-character EE0 / EE1 / EE2 on a Goodman door = GR9S96. Same one-PS physics, different card — use that chart.

Test points

Pressure switch
One NO switch. Closed only after inducer is up. There is no high-fire hose.
Manifold
Single-stage plate value only — no low/high pair. Rating plate wins.
Flame rod
Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use an 80% Norton chart.
ECM taps
Heat default F02. Cool/Y/G default F04. F01 not recommended for heating (SS p.7). Rise is cabinet-specific (25–55 on 0403AN through 35–65 on 80–120 kBtu).

Gotchas

  • Looks like AR9T96 until you count pressure-switch hoses. One hose = this page. Two hoses = AR9T96.
  • Goodman GR9S96 is not this door card. GR9S96 speaks EE0/EE1/EE2. This Amana card is E0–E7 on 0140F20003-B.
  • LPM-33 is the LP kit on both upflow and downflow. Do not grab LPM-34 (AR9T96 / ARVT96) or LPM-31 (AR9S80).
  • F01 on heat is an E3 callback. SS marks it not recommended for heating. Leave heat on F02 unless the rise chart says otherwise.
  • Bottom return: unfold the flanges. SS notes ~18% airflow loss if you leave them folded.
  • 1205D is 3" vent only. A 2" concentric (72950) is not listed for that cabinet — use 72951.
  • A leftover W2 from a previous two-stage furnace does nothing useful here and confuses the next tech. Cap it.

Related plates

  • amana-ar9t96 — Two-stage 9-speed cousin — dual PS, 0140F20004-B, E8/E9 high fire. Wrong chart if you only have one hose.
  • amana-ar9s80 — 80% single-stage 9-speed — Cat I 4" metal vent, 0140F20001-B, LPM-31. E2 is a chimney, not a trap.
  • amana-arvt96 — ComfortBridge two-stage VS R-32. Triple 7-seg + serial ECM. Not this tap IFC.
  • amana-am9s96 — Older single-stage 96% flash sibling. LED 1–9, not this 7-seg E-card.
  • goodman-gr9s96 — Goodman single-stage 9-speed cousin — EE0/EE1/EE2 three-character card, not this E0–E7 door.