Cross-brand lookup from FieldBench plates. Carrier 45 is not Rheem 45. Prefer the plate chart when you have it.
Amana ALXS4B
No Y Outdoor silent
No 24 VAC at the contactor or the coil is open.
Amana ALXS4B
Hum / no start Cap / start
Compressor hums, outdoor fan may run.
Amana ALXS4B
HPS High pressure
Outdoor airflow, overcharge, or restriction.
Amana ALXS4B
LPS / freeze Low pressure
Charge, indoor airflow, metering.
Amana ALXT7C
HPS High pressure
Outdoor airflow, overcharge, or restriction opened the high-pressure switch.
Amana ALXT7C
LPS Low pressure / freeze
Suction dropped out — charge, indoor airflow, or TXV.
Amana ALXT7C
Comm Indoor/outdoor data
ComfortBridge data pair only. Invalid as a diagnosis on a 24V Y1/Y2 hookup.
Amana AM9S96
1 flash Retry lockout
Ignition retries exceeded.
Amana AM9S96
2 flash PS closed, inducer off
Single switch welded or IFC input shorted.
Amana AM9S96
3 flash PS open, inducer on
Draft / trap / hose / inducer.
Amana AM9S96
4 flash Open limit
Airflow or overfire.
Amana AM9S96
5 flash Flame with valve off
Leaking valve or false flame sense.
Amana AM9S96
6 flash Rollout open
Flame containment.
Amana AM9S96
7 flash Low flame
Weak µA.
Amana AM9S96
8 flash Igniter fault
Open / cracked HSI.
Amana AM9S96
9 flash Polarity / ground
L1/N or chassis ground.
Amana AMVC96
idle / Ht1 / Ht2 / CF / CL1 / CL2 Status, not a fault
Normal run states on the triple display. idle = standby. Ht1 / Ht2 = low / high heat. CF = continuous fan. CL1 / CL2 = cooling stage.
Amana AMVC96
E0 System / ignition lockout
Control failed to sense flame after 3 full ignition retries and shut off gas. Auto-resets after 1 hour (or a tstat cycle).
Amana AMVC96
E1 Low-stage PS stuck closed
Low-stage pressure switch is made with the inducer off. Control waits for the fault to clear.
Amana AMVC96
E2 Low-stage PS stuck open
Inducer is on low and the low-stage switch did not close within 5 minutes. Then 1-hour lockout and retry.
Amana AMVC96
E3 Open primary / aux / rollout limit
A limit opened. Both blowers typically run until it recloses. Airflow or overfire — not a charge problem. Rollout is still a manual-reset hazard.
Amana AMVC96
E4 Flame sensed with no call for heat
Rod sees flame with both solenoids de-energized. Control runs circulator and inducer and will not fire again.
Amana AMVC96
E5 Open 24V fuse
Low-voltage fuse on the IFC is open. All furnace operation is inhibited except the error display.
Amana AMVC96
E6 Low flame-sense µA
Flame is present but the micro-amp signal is below the IFC threshold.
Amana AMVC96
E7 Igniter open / no-ground
Igniter is open, not connected, or the IFC failed its ground check on the igniter circuit.
Amana AMVC96
E8 High-stage PS stuck closed
High-stage pressure switch is made with the inducer not on high. Furnace runs low only regardless of demand.
Amana AMVC96
E9 High-stage PS stuck open
Inducer on high, high-stage switch never closes. Classic ‘runs on low, will not go high.’
Amana AMVC96
EA Reversed polarity / poor ground
L1/N reversed or chassis ground missing. HSI and flame sense both suffer. Furnace will not operate.
Amana AMVC96
EE No 115V to control / internal / door switch
No line voltage reaching the IFC, door switch open, or an internal control condition. This is power, not a ComfortBridge data-pair code.
Amana AMVC96
b0 ECM blower not running
IFC commanded the serial ECM and does not detect it running. Furnace will not operate.
Amana AMVC96
b1 ECM communications lost
IFC cannot communicate with the variable-speed blower. Furnace will not operate.
Amana AMVC96
b2 Motor HP mismatch vs shared-data set
Connected motor horsepower does not match the value in the furnace shared-data set. Furnace will not operate.
Amana AMVC96
b3 Motor limiting (power / speed / temp)
ECM is folding back on power, speed, or temperature. Furnace keeps running at reduced CFM.
Amana AMVC96
b4 / b5 / b7 Motor trip / locked rotor / failed start
b4 = lost rotor or overload trip (shuts down and retries). b5 = locked rotor after 10 start attempts. b7 = motor parameters missing or failed to start after 40 attempts.
Amana AMVC96
b9 Low indoor airflow
Indoor airflow fell below the calculated minimum. Furnace stages down (high to low) and will halt if CFM reaches 0.
Amana AMVC96
d0 / d4 Shared data / memory card
d0 = IFC has no shared-data set (replacement board, missing card) and cannot drive the serial ECM or calculate CFM. d4 = card rejected (wrong model card).
Amana AMVM97
idle / Ht / CF Status, not a fault
Normal run states. idle = standby. Ht = heat running (capacity is a percent, not Ht1/Ht2 stages). CF = continuous fan.
Amana AMVM97
E0 System / ignition lockout
Failed to sense flame after 3 retries. 1-hour auto reset.
Amana AMVM97
E2 Pressure-band open / inducer will not prove
Variable inducer is running and the pressure switch / band for that rate never made. Same 96% trap/hose/vent physics as other Amana condensing furnaces — not ‘unplug the low-fire tee.’
Amana AMVM97
E3 Open primary / aux / rollout limit
Limit opened. Airflow or overfire. Rollout is still a manual-reset hazard.
Amana AMVM97
E4 Flame sensed with no call for heat
Rod sees flame with the modulating valve commanded closed.
Amana AMVM97
E5 Open 24V fuse
Low-voltage fuse open. Operation inhibited except the display.
Amana AMVM97
E6 Low flame-sense µA
Flame present, signal below threshold. Lazy flame at a low modulating rate is a common miss.
Amana AMVM97
E7 Igniter open / no-ground
Igniter open, unplugged, or ground check failed.
Amana AMVM97
E9 High-capacity pressure band open
Inducer will not make the high-rate draft band. This is not ‘the high-fire PS tee on a two-stage collector.’ The unit may run at a reduced percent and never reach high fire.
Amana AMVM97
EA Reversed polarity / poor ground
L1/N reversed or chassis ground missing. Furnace will not operate.
Amana AMVM97
EE No 115V to control / internal / door switch
No line voltage, door switch open, or internal control condition. This is power, not a data-pair code.
Amana AMVM97
b0 ECM blower not running
IFC commanded the serial ECM and does not detect it running.
Amana AMVM97
b1 ECM communications lost
IFC cannot talk to the variable-speed blower.
Amana AMVM97
b2 / b3 / b9 Motor HP / limiting / low CFM
b2 = motor HP does not match the shared-data set. b3 = motor folding back on power/speed/temp. b9 = airflow below calculated minimum.
Amana AMVM97
d0 / d4 Shared data / memory card
d0 = no shared-data set on a replacement IFC. d4 = wrong-model card.
Amana AR9S80
E0 Retry / recycle lockout
Too many failed ignition attempts or flame losses on this call.
Amana AR9S80
E1 PS stuck closed
The only pressure switch is made with the inducer off.
Amana AR9S80
E2 PS open — metal-vent draft
Inducer is on and the only switch will not close. This is a chimney / B-vent / 4" metal / inducer call — not a drowned 96% trap.
Amana AR9S80
E3 Open high limit
Primary limit opened. Airflow or overfire.
Amana AR9S80
E4 Flame when valve should be off
Rod sees flame with the solenoid de-energized.
Amana AR9S80
E5 Open fuse
24 V fuse on the IFC is open.
Amana AR9S80
E6 Low flame signal
Flame present, µA below threshold.
Amana AR9S80
E7 Igniter relay fault
IFC did not see the igniter circuit behave as commanded.
Amana AR9S80
EA Line polarity / ground
L1/N reversed or chassis ground missing.
Amana AR9S80
Eb / Ec Gas valve circuit
Internal (Eb) or external (Ec) gas-valve electrical fault.
Amana AR9S80
Ed Open rollout
Manual-reset rollout. Treat as flame outside the exchanger until proven otherwise.
Amana AR9S80
En Igniter open
Igniter circuit measures open.
Amana AR9S80
EEH Grounding error
IFC failed its ground check (sister to EA).
Amana AR9S80
TWIN Twin error
Twinning miswire or twin terminal active on a standalone unit. Door card lists TWIN on 0140F20001-B.
Amana AR9S80
LE1 Low circulator current
9-speed ECM current too low.
Amana AR9S80
FE3 / LE4 / SE5 / rE6 A2L mitigation
Leak / comm / relay alarm from the A2L board when paired with an R-32 / A2L outdoor.
Amana AR9S96
E0 Retry / recycle lockout
Too many failed ignition attempts or flame losses on this call.
Amana AR9S96
E1 PS stuck closed
The only pressure switch is made with the inducer off.
Amana AR9S96
E2 PS open
Inducer is on and the only switch will not close. Classic overnight 96% collector / trap call.
Amana AR9S96
E3 Open high limit
Primary limit opened. Airflow or overfire — not a charge problem.
Amana AR9S96
E4 Flame when valve should be off
Rod sees flame with the solenoid de-energized.
Amana AR9S96
E5 Open fuse
3 A (typical) automotive fuse on the IFC is open.
Amana AR9S96
E6 Low flame signal
Flame is present but µA is below the IFC threshold.
Amana AR9S96
E7 Igniter relay fault
IFC did not see the igniter circuit behave as commanded.
Amana AR9S96
EA Line polarity / ground
L1/N reversed or chassis ground missing. HSI and flame sense both suffer.
Amana AR9S96
Eb / Ec Gas valve circuit
Internal (Eb) or external (Ec) gas-valve electrical fault.
Amana AR9S96
Ed Open rollout
Manual-reset rollout opened. Treat as flame outside the exchanger until proven otherwise.
Amana AR9S96
En Igniter open
Igniter circuit measures open.
Amana AR9S96
EEH Grounding error
IFC failed its ground check (sister to EA).